Three Flashes – Open in the Safety Switch Circuit
When there is a THREE ash troubleshooting code, the unit is indicating that the limit
switch or ame roll out switch is open.
The limit switch is ignored unless a call for heat is present (R to W energized).
If the limit switch is open and a call for heat is present, then:
The control de-energizes the gas valve, runs the blower motor and runs
the power exhauster.
The control will ash three times on the LED unit the limit switch closes.
When the switch re-closes or the call for heat is lost, the control runs
the power exhauster through post-purge and runs the blower through
the fan off delay.
The control will return to normal operation after the blower off
delay is completed.
Possible Causes:
Open or short in safety circuit (ame roll out switches some and some limit
switches are manual reset):
Check for open contacts on switches in safety circuit. Reset ame roll
out switches and manual reset limit switches.
Check wiring for loose connections.
Replace defective limits if they will not reset automatically or manually
after the unit heater has cooled.
Defective board, not letting 24 VAC through limits.
¨ For more information on xing or replacing a defective board,
reference page 23.