Hot Dawg
®
Troubleshooting Guide16
Four Flashes – Unit Sparks, Lights Flame and
Shuts Down After 10 Seconds
The information below is related to situations where the unit DOES SPARK and then
SHUTS DOWN within 10 seconds:
This usually occurs as a result if the safety switch circuit is open:
Pressure switch is open
Unit Sequence:
Green light on, call for heat
Power exhauster cycles on, burner lights, no yellow ame light on board,
burner shuts down after 10 seconds. Fan motor never cycles on.
Possible Causes:
Reversed polarity:
To check for reversed polarity:
1. Remove the call for heat
2. Measure voltage across terminal L1 and case. It should be 115 VAC
3. Measure voltage across terminal NEUTRAL and case.
It should be 0 VAC
4. If the readings are backwards, shut off power, then reverse LI and
neutral wires coming from the panel to the unit
Loose ame sensor wire
Dirty or defective ame sensor, not sending micro-amps to board:
Clean sensor with emery cloth
If issue is not resolved, verify and replace sensor
Defective board
Getting correct micro-amps from sensor, but not allowing unit to ignite
For more information on xing or replacing a defective board,
reference page 23.