19
Five Flashes – Twin Communication Fault
The information below is related to situations where the troubleshooting code ashes
FIVE times:
Twin Communication Fault:
Occurs if the 24 VAC supply to the twins are not in phase with each other or
power is removed from one of the twins.
While a twin fault exists, the control does not respond to thermostat
commands, and the green light will ash ve times.
Open limit and undesired ame response are still operational
The control continually tries to establish communication and automatically
resumes normal operation when communication is re-established
If a twin fault occurs during a heat cycle, both furnaces will terminate the
call immediately
The only chance for blower mis-synchronization is if the blower off delays
are set differently on the twins
If a twin fault occurs during high speed fan or continuous fan operation,
both controls will shut the blowers off immediately.
If a twin communication terminal is not in use and the unit is showing a
troubleshooting code of ve ashes, the board may be defective.