Troubleshooting Guide20
Six Flashes – Main Air Mover Doesn’t Cycle On
The information below is related to situations where the main air mover
DOES NOT cycle on:
This usually occurs as a result of an open in the safety switch circuit:
Limit switch or ame roll out switch is open
Unit Sequence:
Green light on, call for heat, power exhauster cycles on, pre-purge
24 VAC power present through pressure switch, limits and to valve
Igniter sparks, burner cycles on, yellow ame light turns on, board is on
After three to four minutes, unit goes out on a limit switch, yellow light turns
off, green light then ash six times
Possible Causes:
Loose wires
Check all wiring for a loose wire
Defective motor
115 VAC at EAC and neutral terminals on board, but motor does
not turn on
Defective board
115 VAC not present at EAC and neutral terminals
For more information on xing or replacing a defective board,
reference page 23.