EasyManua.ls Logo

Moeller ps4-201-mm1 - 2 Engineering; Electromagnetic compatibility (EMC); Connections

Moeller ps4-201-mm1
94 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15
04/99 AWB 27-1184 GB
2 Engineering
Electromagnetic
compatibility (EMC)
Observe the engineering instructions in the manual
“EMC Engineering Guidelines for Automation
Systems” (AWB27-1287GB).
Connections Screened data and signal cables
Route screened data and signal cables on the left
and the right of the device along the shortest
possible distance and connect the screen braid
to the ground terminal using a low-impedance
connection and large contact areas (See Fig. 4,
item
).
Connect the screen braid with the metal sleeve of
the plug connector (DIN plugs)
.
Insulate the end of the screen braid as close as
possible to the signal cable entry
.

Related product manuals