EasyManua.ls Logo

Moore Industries THZ3 - Page 109

Moore Industries THZ3
140 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.miinet.comMoore Industries-International, Inc.
- 109 -
User’s Manual
238-741-00K
May 2019
Programmable Smart HART Temperature Transmitter
THZ
3
/ TDZ
3
Range Alarms This menu allows you to enable and configure each of the 4 Range Alarms.
See Section 1 more information on this feature.
Each alarm has the following settings (see Figure 5.43) :
Enable: [Disabled] Enables or Disables the Range Alarm
Latching: [Disabled] Enables or Disables latching of the alarm. Non-latching alarms
return to a non-alarm state whenever the process input returns to a non-alarm level. Once
tripped, a latching alarm remains in an alarm state until the input returns to a non-alarm
level and is reset.
Source: [Primary Variable] The Variable to be used as a source for the Range Alarm
Response: [Warning] How to react if the specified condition occurs: Warning - Sends a
warning message to the HART Handheld/DTM, TDZ
3
display and sets a HART status bit.
Alarm - Sends the AO into fail mode and sends an alarm message to the HART Handheld/
DTM, TDZ
3
display. It also sets a (different) HART status bit.
Assertion: [Out of Range] Indicates if the Range Alarm should detect if the source
variable goes Out of range, or goes In range.
Low: [0.00] The defined lower limit of the Range Alarm
High: [100.00] The defined upper limit of the Range Alarm
UnLatch Range Alarm: Reset an actively latched range alarm provided that the input has
returned to a non-alarm level.
Note: If a Range Alarm Response is set to Alarm, the AO will always perform a fail response
even if the Source Device Variable is not assigned to the PV.
SECTION 5
Figure 5.43.B. Additional Functions Menu for Range Alarms

Related product manuals