Programmable Smart HART Temperature Transmitter
THZ
3
/ TDZ
3
Quick Start Guide
THZ3/TDZ3 Quick Start Guide
The THZ
3
/TDZ
3
is ready to install and is either set up with your specified configuration or the
default configuration below. If you need to change any parameters this can be done using a HART
handheld configurator or FDT/DTM application (see Sections 4 & 5).
After programming your transmitter, install the unit into your application using the connection
diagrams and terminal designation table located in this manual.
Default Configuration - Single Sensor Mode
Sensor 1: 4 Wire RTD, Pt3850, 100 Ohms, 0-100º C
Broken Wire: Enabled
Broken Wire Holdoff: Disabled, 0 seconds
Sensor 2: Disabled
Filter: 60Hz
Running Average Filter: DISABLED, Setting: 1
PV Damping: DISABLED, 0 seconds
(TDZ
3
) Display Source: Primary Variable (PV)
(TDZ
3
) Decimal Places: Auto
Analog Output: 4-20mA
Analog Output Under Range Min Value: 3.8mA
Analog Output Over Range Max Value: 21.6mA
Sensor Fail Mode: High, 23.6mA
PV is= Sensor 1
SV is= RJC Temperature
TV is= Sensor 1
QV is= Sensor 1
Input Quality Alarms: Allow measurement out of conformance range = On,
Allow Limited = Off, Allow Dropping = Off
Advanced Features: Disabled