EasyManua.ls Logo

Moore Industries THZ3 - Page 12

Moore Industries THZ3
140 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.miinet.com Moore Industries-International, Inc.
- 12 -
User’s Manual
238-741-00K
May 2019
Programmable Smart HART Temperature Transmitter
THZ
3
/ TDZ
3
SECTION 1
2ohms
40ohms
35ohms
WARNING
RTD WIRE
RESISTANCE
RTD Wire
Resistance
T/C Circuit
Resistance
CAPTURED
VALUE
ALARM
2ohms
35ohms
Dierent Values Same Values
RTD WIRE
RESISTANCE
CAPTURED
VALUE
WARNING
& ALARM
200ohms
4,000ohms
3,500ohms 3,500ohms
WARNING
T/C CIRCUIT
RESISTANCE
CAPTURED
VALUE
ALARM
200ohms
Dierent Values Same Values
T/C CIRCUIT
RESISTANCE
CAPTURED
VALUE
WARNING
& ALARM
TIME
Initial
Minimal
Dierence
Typical Drift Over Time
T
USER
DEFINED
DRIFT
LIMITS
Drift Alert
Activated
Sensor Drift Detection
Drifting in sensors occurs from a number of di󰀨erent causes including environmental
contamination, vibration, and extreme temperature uctuations. This can lead to false sensor
readings. The THZ
3
/TDZ
3
can be congured to detect these false readings by using a Range
Alarm to monitor the absolute di󰀨erential between two sensors (i.e. RTD & T/C or two RTDs or
T/Cs) at the same point. This method can provide a range alarm warning or alarm to indicate
that there is an issue with one of the sensors. See Chart below for clarication.
In this example a Range Alarm is set with the Absolute Di󰀨erential as the source. An out of
range warning or alarm is congured with the low and high limits set to 0C° to 5C° respectively,
creating an alarm when Sensor 1 and Sensor 2 readings drift apart by more than 5C°.
Note: When setting the drift limit please allow for sensor tolerances and differences in sensor
response times to avoid false drift alerts.
Corrosion Detection
Corrosion of the sensor connections is primarily caused by oxidation or electrolysis which can
lead to inaccurate readings with RTD measurements. The THZ
3
/TDZ
3
is able to detect corrosion
on 3W or 4W RTDs by measuring the change in compensating lead wire resistance between
terminals 3 and 4 providing an alert when preset value limits are exceeded.
Additionally the THZ
3
/TDZ
3
monitors the status of T/C circuits. High resistance values in T/C
circuits could indicate a potential impending T/C burnout.

Related product manuals