www.miinet.com Moore Industries-International, Inc.
- 60 -
User’s Manual
238-741-00K
May 2019
Programmable Smart HART Temperature Transmitter
THZ
3
/ TDZ
3
SECTION 4
-S1 2Wire Offset: This setting is to offset the wire resistance of the 2Wire sensor cable,
and will help the accuracy of the measurement. Selecting this will display current Sensor
1 2Wire Offset and allow you to make changes as required. If you make a change select
desired parameter and hit the ENTER button to return to previous screen in Menu.
-S1 Sensor Information: selecting this will display the Sensor 1, Sensor Information
menu.
The following will be displayed with your set parameters:
-Sensor 1 USL: Upper Sensor Limit
-Sensor 1 LSL: Lower Sensor Limit
-Sensor 1 Min Span: Minimum Span
-Sensor 1 s/n: Sensor 1 Serial Number
Hit the HOME button to return to home menu.
-S1 Scaling: Selecting this will prompt menu shown in Figure 4.6. The Following options
are displayed Sensor 1 Scl En, Sensor 1 EGU, Sensor 1 Input Min, Sensor 1 Max.,
Sensor 1 Scale Min., and Sensor 1 Scale Max. Here you can Enable or Disable
Sensor 1 Scaling, select an EGU for Sensor 1, enter Sensor 1 Input Min/Max and Sensor
1 Scale Min/Max.
-S1 Custom Curve: Selecting this will prompt menu shown in Figure 4.7. This allows
enabling/disabling custom curve, setting engineering units and selecting 1 of 4 predefined
Custom Curves to apply to Sensor 1.
Note: The
Custom Curve
menu is only visible if Advance Settings is Enabled. Custom
Curves have to be generated and saved in the unit using the DTM before they can be assigned
to the Sensor.
Note: After making all desired changes enter SEND to update the unit.
Sensor 2:
Selecting this will prompt the same menu options as previous Sensor 1 conguration. The same
parameters features and setting options will be made available to change/update as Sensor 1
but these changes/update will be made to Sensor 2 when done within this menu. Refer to Figure
4.5 for clarication.
Hit the HOME button to return to home menu.
Note: After making all desired changes enter SEND to update the unit.
After entering SEND you can choose to SAVE, this will prompt menu allowing to choose desired
Location (Internal Flash or System Card), Name, and Cong Type.
Note: When selecting a Location where to save file to, both locations are on the HART
handheld communicator, “Internal Flash” stores file directly into the HART handheld
communicator internal flash. While selecting “System Card” allows you to save to the installed
system card (SD memory card).
Note: After making all desired changes enter SEND to update the unit.