The HART Settings menu provides access to the following HART settings:
See Figure 5.30 for further clarication.
Poll Address (0-63) [0] – This is the HART Polling Address, enter a number from 0-63.
Number of Response Preambles (5-20) [5]– Enter the number of Preamble Characters
(0xFF) that are sent before any HART response message. This command selects the
minimum number of preambles to be sent by a device before the start of a response
packet in the HART message. A longer preamble means slower communication. The
number of preambles may need to be manually increased for some HART hosts, if there
are missed messages or communication errors.
Tag– Place a unique label that corresponds to your instruments location or specific usage
(8 characters maximum).
Long Tag– Place a unique label that corresponds to your instruments location or specific usage
(32 characters maximum).
Descriptor– Place text that is used as a description of how the instrument is being used (16
characters, maximum).
Message– Place additional information that may be helpful in describing the instrument or its
use (32 characters,maximum).
Final Assembly Number [0] – You may enter a number that is used for identification purposes,
and is associated with the field device (8 characters, maximum).
Programmed DateThis is a read-only value, displays the date this unit was programmed at
factory.
Device Id (S/N) This is a read-only value that uniquely identifies the field device when
combined with the manufacturer identification and device type.
Hardware Revision This is a read-only value corresponds to the revision of the electronics
hardware of the field device.
HART Revision This is a read-only corresponds to the HART revision installed on field device.
Firmware Revision This is a read-only value corresponds to the revision of the Firmware of
the field device.