Sampling Rate (all
channels)
Built-in Resistor for
Current Input
±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
Internal register: 400 ohms
Note: 24 V of external power is required when loading > 1000 ohms.
PT50, PT100, PT200, PT500, PT1000
1–310, 1–620, 1–1250, 1–2200 ohms
12 samples/sec (all channels)
±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
±78.126 mV, ±39.062 mV, ±19.532 mV
Fault and Overvoltage
protection
±35 VDC (power off); +30 VDC, -25 VDC
(power on)
12 samples/sec (all channels)
±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
Installation
Connecting the Power
Connect the +12 to +36 VDC power line to the ioLogik E1200’s terminal
block V+ terminal; connect the ground from the power supply to the V-
terminal. Connect the ground pin ( ) if earth ground is available.
For safety reasons, wires connecting the power supply should be
at least 2 mm in diameter (e.g., 12 gauge wires).