5 Overview of parameters
27
Parameter Setting range Factory setting Current setting
Motor runtime 0...30 s 0.0 s
Manual/Automatic Manual, Auto Manual
Local/Remote Local, Remote Local
Configuration > Parallel operation
1)
Parallel operation acti-
vation
On, Off On
Parallel operation
method
Circulating reac-
tive current; Mas-
ter; Follower; Au-
to synchroniza-
tion
Circulating reac-
tive current
Parallel operation
group
None; Group 1;
Group 2; Group 1
and Group 2
None
CAN address 0...16 0
Simplex mode block-
ing.
On, Off On
Circulating reactive
current sensitivity
0...100 % 0.0 %
Circulating reactive
current blocking
0.5...40 % 20.0 %
Master/follower cur-
rent blocking
Blocking, Off Blocking
Parallel error delay 1...999 s 10 s
Follower tapping di-
rection
Standard, Swap-
ped
Standard