44
Settings Parameters
GB
Model 9010/9020 SIL
AC4 P10/ P14/ P18 Alarm Delay C=0, W=0. A=0 (Disabled)
AC4 P19
Analog Output Settings (in a normal operating
condition)
4-20 mA
AC4 P20 Analog Output Settings (in a failure condition) 2 mA
AC4 P21 Decimal Places 0
AC4 P27 Region EU (Europe)
AC6 P2 ATEX Mode A (Enabled)
AC6 P3 Startup Sound on (Enabled)
AC6 P4 Key Press Sound on (Enabled)
AC6 P8 Beeper Mode OFF
AC7 P1 Modbus Address 1
AC7 P2 RS485 Baud Rate 38400 bd
AC7 P3 Ethernet Configuration DHCP
AC7 P4 Static IP Address 192.168.1.23
AC7 P5 Subnet Mask 255.255.255.0
AC7 P6 Gateway IP Address 192.168.1.1
AC7 P7 DNS IP Address 192.168.1.1
AC52 P1 Output Type 1 (Relays)
AC52 P2 Detector Type 1 (Catalytic detector)
AC223 Password 0001 (Enabled)
Access Code Description Default Value