44
4 Operation US
Table 13 IR Sensor Default Settings
Gas
(Code)
Range Range
Default
Unit
Default
Warn
Default
Warn
Default AO
1
(mA)
Alarm
Default
Alarm
DefaultAO
1
(mA)
Alarm
Action
Default
Cal
Level
Default
Alarm
Min
Alarm
Max
Cal
Level
Min
Cal
Level
Max
Display
Resolution
2
IR400
5%
Methane
(R31)
0-100 0-100 %LEL 30 8.8 60 13.6 Increasing
Non-Latch
50 5 60 Fixed at 50% 1
IR400
4.4%
Methane
(R43)
0-100 0-100 %LEL 30 8.8 60 13.6 Increasing
Non-Latch
50 5 60 Fixed at 50% 1
IR400
2.1%
Propane
(R32)
0-100 0-100 %LEL 30 8.8 60 13.6 Increasing
Non-Latch
50 5 60 Fixed at 50%
LEL
1
IR400
1.7%
Propane
(R44)
0-100 0-100 %LEL 30 8.8 60 13.6 Increasing
Non-Latch
50 5 60 Fixed at 50%
LEL
1
IR400
Hexane
(R34)
0-100 0-100 % LEL 30 8.8 60 13.6 Increasing
Non-Latch
50 5 60 Fixed at 50%
LEL
1
IR400
Pentane
(R35)
0-100 0-100 % LEL 30 8.8 60 13.6 Increasing
Non-Latch
50 5 60 Fixed at 50%
LEL
1
IR400
Ethylene
0-100 0-100 % LEL 30 8.8 60 13.6 Increasing
Non-Latch
50 5 60 Fixed at 50%
LEL
1