8.19.2 Differential pressure gage – Alarm function check
WARNING
Fuels are combustible and explosive.
Risk of fire and explosion!
• Avoid open flames, electrical sparks and ignition sources.
• Do not smoke.
• Wear protective clothing, protective gloves, and safety glasses / facial protection.
Checking differential pressure gage alarm function
1. Switch on fuel treatment system (→ Page 54).
2. Set the alarm points at the differential pressure gage to zero.
Result: Alarm is issued after preset time.
3. Reset alarm points at differential pressure gage.
M015650/06E 2018-05 | Fuel Supply System | 155