322 – AL Wiring Cylinder A2
PV-Number:
Cause Corrective action
Short circuit fault in the injector
wiring for cylinder A2 or injector
defective.
1. Check wiring of affected injector (→ Page 160).
2. Check injector.
3. Replace injector (→ Page 112).
4. Contact Service.
323 – AL Wiring Cylinder A3
PV-Number:
Cause Corrective action
Short circuit fault in the injector
wiring for cylinder A3 or injector
defective.
1. Check wiring of affected injector (→ Page 160).
2. Check injector.
3. Replace injector (→ Page 112).
4. Contact Service.
324 – AL Wiring Cylinder A4
PV-Number:
Cause Corrective action
Short circuit fault in the injector
wiring for cylinder A4 or injector
defective.
1. Check wiring of affected injector (→ Page 160).
2. Check injector.
3. Replace injector (→ Page 112).
4. Contact Service.
325 – AL Wiring Cylinder A5
PV-Number:
Cause Corrective action
Short circuit fault in the injector
wiring for cylinder A5 or injector
defective.
1. Check wiring of affected injector (→ Page 160).
2. Check injector.
3. Replace injector (→ Page 112).
4. Contact Service.
326 – AL Wiring Cylinder A6
PV-Number:
Cause Corrective action
Short circuit fault in the injector
wiring for cylinder A6 or injector
defective.
1. Check wiring of affected injector (→ Page 160).
2. Check injector.
3. Replace injector (→ Page 112).
4. Contact Service.
M015650/06E 2018-05 | Troubleshooting | 79
TIM-ID: 0000082479 - 001