356 – AL Open Load Cylinder B8
PV-Number:
Cause Corrective action
Disruption fault in injector wiring
to cylinder B8.
1. Check wiring of affected injector (→ Page 160).
2. Check injector.
3. Replace injector (→ Page 112).
4. Contact Service.
361 – AL Power Stage Low
PV-Number:
Cause Corrective action
The output stage voltage to
control the injectors is too low.
1. Check power supply (plant).
2. Check engine wiring (→ Page 160).
3. Contact Service.
362 – AL Power Stage High
PV-Number:
Cause Corrective action
The output stage voltage to
control the injectors is too high.
1. Check power supply (plant).
2. Contact Service.
363 – AL Stop Power Stage
PV-Number:
Cause Corrective action
Engine emergency stop because
the output stage voltage to
control the injectors is too low.
1. Check power supply (plant).
2. Check engine wiring (→ Page 160).
3. Contact Service.
365 – AL Stop MV-Wiring Ground
PV-Number:
Cause Corrective action
Short circuit of injector positive
connection to ground of one or
more injectors. Short circuit of
injector negative connection to
ground of one or more injectors.
1. Check injector wiring (→ Page 160).
2. Check injectors .
3. Replace injector (→ Page 112).
4. Contact Service.
371 – AL Wiring TO 1
PV-Number:
Cause Corrective action
Short circuit or wire break on
transistor output 1 (TO 1).
1. Check engine wiring (→ Page 160).
2. Contact Service.
M015650/06E 2018-05 | Troubleshooting | 85
TIM-ID: 0000082479 - 001