NOTE
Horizontal ducts must be installed with a slight decline away from the dehumidifier to
drain possible condensation. The decline must be at least 2 cm/m of duct. Drainage
holes (5 mm) should be made at low points of the duct to prevent water accumulation.
Fasten wire netting with a mesh width of approximately 10 mm in the outer end of the duct.
Wet air hoses are usually guided outdoors. In large premises where the dehumidifier is outside of the
space to be dehumidified, the wet air must be ducted away from the unit with a hose of minimum length
2 metres. Make sure that the wet air is not sucked back into the unit and that the wet air does not blow
against moisture sensitive objects.
5.5.3. Connecting the wet air hose
The wet air outlet is hidden for transportation purposes.
The outlet diameter is 50 mm.
1. Pull out the outlet.
2. Turn the outlet clockwise to lock it in position.
3. Connect the hose.
NOTE
Maximum length of the wet air hose is 6 metres.
ComDry M190Y Dehumidifier