DehumidierML420-MLT1400
Partnumber170-013448–005170-013448–004170-013448–003170-013448–002170-013448–001
A
Ø100Ø125Ø160Ø200Ø250
B
Seesection9.1,Dimensionsandservicespace.
L(mm)
210210200140150
ML420XX
ML690XX
MLT800XX
ML1100XX
ML1350XX
MLT1400XX
CA CA
CA
UTION! UTION!
UTION!
Thedehumidierhasbeendesignedtooperateatspecicprocessairowscorrespondingtothefansizes
installed.
Theprocessairanddryairductsshouldbethesamediameter.Thesameappliestothereactivationair
andwetairducts.
Thelengthofductworkmustbekeptasshortaspossibletominimisestaticairpressurelosses.
Tomaintainperformance,allrigidprocessorreactivationairductworkjointsmustbeairandvapour
tight.
Theprocessairductworkmustbeinsulatedtopreventcondensationdevelopingontheoutsideofthe
duct,wheneverthetemperatureoftheairwithintheductfallsbelowthedewpointtemperatureofthe
ambientairthroughwhichtheductworkisrouted.
Theductsmustalwaysbeinsulatedwhenthereisariskoffreezing.
Thewetairleavingthedehumidierwill,becauseofhighmoisturecontent,condenseontheinsideduct
walls.Byinsulatingtheducts,theamountofcondensateisreduced.
Horizontalwetairductsmustbeinstalledwithaslightdecline(awayfromthedehumidier)todrain
awaypossiblecondensation.Suitablecondensationdrainsmustbeinstalledatlowpointsinthewet
airoutletduct,seeFigure4.7.
Ensurethataccessforoperationandservicingisnotrestrictedwhendesigningandinstallingducting.
Formoreinformation,refertosection9.1,Dimensionsandservicespace.
Toreducenoiseand/orvibrationbeingtransmittedalongrigidducts,goodquality,airtightexible
connectionscanbetted.
Ductsmounteddirectlyontotheunitmustbeindependentlysupportedtominimisetheloadontheunit.
Dampersforadjustingtheairowsmustbeinstalledinthesupplyairoutletandreactivationairinlet
ducts.Correctairowsareessentialfortheoperatingefciencyoftheunit.Forairowadjustment
instructions,seesection5.3,Airowcheckandadjustment.
Thetotalpressuredropintheprocessandreactivationductworkmustnotexceedtheavailablepressure
ofthefansttedtothedehumidier.Fordetailsofminimumavailablestaticpressure,seesection
9.3,Technicaldata.