4.6PrecautionarymeasuresforunitswithLIdesiccantrotor
ThestandarddeliveryisMuntershighperformancedesiccantrotorHPS(HighPerformanceSilicagel).
IfthedehumidierisdeliveredwithanLIrotor(lithiumchloride)itisimportantthattherotordoesnot
becomeloadedwithmoisturewhenthedehumidierisoff.
NOTE!Makesurethatnoairpassingthroughtherotorhasarelativehumiditygreaterthan80%.
Itisrecommendedtoinstallclosingdampersintheprocessandreactivationairinletstoavoidthatairwith
highrelativehumidityisdrawnthroughtherotorandintotheroom.
Thisisparticularlyimportantwhentheprocessairisdrawnfromoutdoors,orwhenthesystemhasbeen
ttedwithapre-cooler.
4.7Electricalconnections
W W
W
ARNING! ARNING!
ARNING!
Allelectricalequipmentconnectionsmustbecarriedoutinaccordancewithlocalregulationsandbyqualied
personnel.Riskofelectricalshock.
W W
W
ARNING! ARNING!
ARNING!
Theunitmustneverbeconnectedtoavoltageorfrequencyotherthanthatforwhichitwasdesigned.Refertothe
unitidenticationplate.
Eachunitissuppliedcompletewithalltheinternalwiringinstalledandconguredinaccordancewiththe
speciedvoltageandfrequencyontheidenticationplate.
NOTE!Thesupplyvoltagemustnotdifferfromthespeciedoperatingvoltagebymorethan+/-10%.
Forconnectiondetails,seetheidenticationplateandthewiringdiagramorsection9.3,Technicaldata.
4.8Externalhumiditysensor
ML-seriesdehumidiersarewiredsothatwhentheunitissettoAUTOmatic,itcanbecontrolledfrom
anexternallymountedhumiditysensor.
Allmodelshaveatwo-stageheater,andcanbecontrolledbyatwo-stagehumiditysensor.Thismethodis
moreefcientandallowsformoreaccuratedehumidicationcontrol.
Theelectricalconnectionsaremadeatterminalsintheelectricalcontrolpanel.Forwiringandconnection
details,seethewiringdiagram.
NOTE!Wherenohumiditysensorisconnectedtotheunit,thedehumidierwillbeoperatingatmaximumoutput
foraslongastheunitisswitchedon.
Aroomhumiditysensoristobemounted1-1.5mabovetheoor.Itmustbepositionedsothatitisnot
directlyexposedtodryairfromtheunitortohumidairowinginthroughopeningdoors.Positionitaway
fromheatsourcesanddirectsunlight.
Thehumiditysensorconnectingcableshouldhaveaconductorareaofnotlessthan
0,75mm
2
andmusthaveaninsulationresistanceratinginexcessof500VAC.
ThehumiditysensormustbedesignedsothatthecontactscloseonarisingRHtocompletethecontrol
circuitandstartthedehumidier.