9.3Technicaldata
Thefollowingisapplicabletounitsttedwithelectricreactivationheater.
ModelML420ML690MLT800ML1100ML1350MLT1400
Processair
(1)
Ratedairow(m
3
/s)0,1160,1920,2220,3050,3750,388
Ratedairow(m
3
/h)420690800110013501400
Minimumavailablestaticpressure(Pa)
(2)
200300200300300300
Fanmotorpower(kW)at50Hz
(3)
0,370,550,551,11,11,1
Fanmotorpower(kW)at60Hz
(3)
0,370,560,661,321,321,32
Reactivationair
(1)
Ratedairow(m
3
/s)0,0430,0710,0430,1130,1360,071
Ratedairow(m
3
/h)155254155408490254
Minimumavailablestaticpressure(Pa)200300200300300300
Fanmotorpower(kW)at50Hz
(3)
-0,370,370,550,550,37
Fanmotorpower(kW)at60Hz
(3)
-0,440,440,660,650,44
Ratedcurrent
Current(amps/phase)3~50Hz200V14,925,5-40,2--
Current(amps/phase)3~60Hz200V14,925,5-40,1--
Current(amps/phase)3~50Hz220V12,62214,936-24,3
Current(amps/phase)3~60Hz220V12,622,515,436,4-24,6
Current(amps/phase)3~50Hz230V12,121,614,935,1-24
Current(amps/phase)3~50Hz380V7,312,78,620,824,414,1
Current(amps/phase)3~60Hz380V7,3138,92124,914,2
Current(amps/phase)3~50Hz400V712,48,520,223,613,8
Current(amps/phase)3~50Hz415V6,712,28,419,823,113,5
Current(amps/phase)3~60Hz440V6,411,37,818,622,312,7
Current(amps/phase)3~60Hz460V6,1117,61821,712,4
Current(amps/phase)3~60Hz480V5,910,87,517,621,112,2
Reactivationheater
Temperatureincreaseacrossheater(°C)959595959595
Reactivationheaterpower(kW)4,26,94,211,113,56,9
Miscellaneousdata
Drivemotorpower(W)20
FiltersG3
IECprotectionclass(unit)IP33
IECprotectionclass(electricalpanel)IP54
FanmotorwindinginsulationclassClassF
DrivemotorwindinginsulationclassClassF
Hightemperaturecut-out(°C)160±5
Burnercontrollersupplyvoltage1~50Hz(VAC)---220/240--
Contactorcoilvoltage(VAC)24
34Technicalspecication190TGB-1035-H1604