EasyManua.ls Logo

Munters ML1350 - Automatic Mode - RH98 or VariDry (Option)

Munters ML1350
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DehumidierML420-MLT1400
4.Setthemodeswitchonthecontrolpanelto”0”andcheckthatboththeindicatorlampsforthe
reactivationheatergoout.
NOTE!Inordertodissipateanyresidualheat,thereactivationairfan,processairfanandthedrivemotorwill
continuetorun(aftertheunithasbeenswitchedoff)untilthetemperaturehasfallenbelow50°C.
5.Checkthattheprocessairfan,reactivationairfananddrivemotorindicatorsgooutwhenthe
temperaturefallsbelow50°C,andthatthepowerconnectedindicatorremainson.
Fordetailsontheoperatorpanel,seesection6.4,Operatorpanel
6.6.2Automaticmodehumiditysensorconnected
Asingleortwostagehumiditysensormustbeconnectedfortheunittoberuninautomaticmode.For
furtherinformation,seesection5.1.2,Single-stagehumiditysensorand5.1.3,Two-stagehumiditysensor.
1.SetthemodeswitchtoAUT.
2.AdjustthehumiditysensorsetpointtothelowestRHvalue.Setthemainpowerswitchto”1”(on).
Checkthatthefollowingindicatorlampsareonandthattheunitisrunning.
Mainssupplyconnectionindicator
Unitrunningindicator*
Bothreactivationheaterindicators*
Bothprocessairandreactivationairfanindicators*
Drivemotorindicator*
NOTE!IfthecurrentRHvalueintheroomtobedehumidiedislowerthanthesetpointonthehumiditysensor,
theaboveindicatorswillnotlightandthedehumidierwillnotstart.
3.Slowlyincreasethehumiditysetpointandcheckthattheunitswitchesoffwhenthesetpointmatchesthe
RHintheroomwherethehumiditysensorisinstalled.
4.Slowlydecreasethehumiditysetpointandcheckthattheunitswitchesonwhenthesetpointfallsbelow
theRHintheroomwherethehumiditysensorisinstalled.
5.Setthemodeswitchonthecontrolpanelto”0”andcheckthatboththeindicatorlampsforthe
reactivationheatergoout.
NOTE!Inorderfortheunit’sheaterstocooldown,thereactivationairfan,processairfanandthedrivemotorwill
continuetorun(aftertheunithasbeenswitchedoff)untilthetemperaturehasfallenbelow50°C.
6.Checkthattheprocessairfan,reactivationairfananddrivemotorindicatorsgooutwhenthe
temperaturefallsbelow50°Candtheunitisrunning,andthatthepowerconnectedindicatorremains
on.
7.AdjustthehumiditysetpointtothedesiredRHvalue.
Fordetailsontheoperatorpanel,seesection6.4,Operatorpanel
6.6.3Automaticmode-RH98orVariDry(option)
IftheunitisttedwithafactoryinstalledRH98orVariDry(option)humiditycontrolsystem,theexternal
humiditysensormustbeinstalledandcorrectlyconnectedtotheunit.Thesamesiterequirementsapplyto
thehumiditysensorandRH98orVariDry,seesection4.8,Externalhumiditysensor.
Formoreoperationaldetails,seeappendix1.6,Humiditycontrolsystem.
1.SetthemodeswitchtoAUT.
22Operation190TGB-1035-H1604

Table of Contents

Related product manuals