EasyManua.ls Logo

Munters ML1350 - Airflow Check and Adjustment

Munters ML1350
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DehumidierML420-MLT1400
5Commissioning
TheML420-MLT1400dehumidiershaveseveralstandardfunctionsthatneedtobesetbeforeinitial
start-up.Someofthefunctionsrequireconnectiontoexternalequipment.
Somefeaturesrequireconnectionofexternalequipment.Forwiringdetails,seethewiringdiagram.
5.1Settingsbeforestart-up
5.1.1Continuousprocessairfanoperation
Standardsettingsautomaticallyactivatetheprocessairfanonlywhendehumidicationisrequired.
However,continuousprocessairowcanbedesirableevenwhendehumidicationisnotrequired.
Continuousprocessairowcanbeset,seethewiringdiagram.
5.1.2Single-stagehumiditysensor
NOTE!Whennohumiditysensorisconnected,thedehumidierwillrunatmaximumeffectcontinuously.
Ifasingle-stagehumiditysensoristted,thiswillswitchthedehumidieronandoff.Asingle-stage
humiditysensorisconnectedaccordingtothewiringdiagram.
Tomaintainaircirculation,preselectcontinuousoperationoftheprocessairfaneventhough
dehumidicationisnotrequired.Forfurtherinformation,seesection5.1.1,Continuousprocessairfanoperation.
5.1.3Two-stagehumiditysensor
NOTE!Whennohumiditysensorisconnected,thedehumidierwillrunatmaximumeffectcontinuously.
Ifatwo-stagehumiditysensorisconnected,thiswillcontrolthereactivationheaterintwostages.The
reactivationpoweriscontrolledonthebasisofthehumiditysensorreadingandthesetpoint.Atwo-stage
humiditysensorisconnectedaccordingtothewiringdiagram.
Tomaintainaircirculation,preselectcontinuousoperationoftheprocessairfaneventhough
dehumidicationisnotrequired.Forfurtherinformation,seesection5.1.1,Continuousprocessairfanoperation.
5.1.4Remotefaultindication
ThePCBdisplaycanbeusedforageneralindicationofthefollowingfaultsonthedehumidier:
Processairfan
Reactivationairfan
Drivemotor
Heater
Auxiliaryequipmentinput
Rotorhasstopped(ifthisoptionisinstalled)
Blockedprocessairlter(ifthisoptionisinstalled)
Blockedreactivationairlter(ifthisoptionisinstalled)
190TGB-1035-H1604Commissioning15