DehumidierML420-MLT1400
ParameterDescriptionPossibleparameterselectionDefaultsetting
05Correctionofthehumiditytransmitter’sread-offvalue0%RHNosettings
10OFF/ONinterval,stage11-15%RH2%RH
(1)
11Offsetstage1-15-+15%RH-1%RH
12OFF/ONinterval,stage21-15%RH6%RH
(2)
13Offsetstage2-15-+15%RH-1%RH
14OFF/ONintervalalarmoutput1-15%RH1%RH
15Offsetfromsetpoint,alarmoutput-15-+15%RH0%RH
30Alarmthresholdtype:0=Notactivated;1=Absolute;2
2=Relative
31Minimumalarmthreshold-100-+100%RH-50%RH
32Maximumalarmthreshold-100-+100%RH10%RH
33Delayforminimumalarm0-99minutes0min.
34Delayformaximumalarm0-99minutes0min.
35Functionofalarmoutput0=monitoralarm1=check1
36Resetalarmwhenthecauseofthealarmisrectied0=No;1=Yes1
37AlarmresettingwhentheSETbuttonispressed0=No;1=Yes1
(displayonly)
40Powerdelayafterpowerfailure0-99minutes0min.
41Forcedrelayfunctionathumiditytransmitterfailure0=Off;1=Humidication;2
2=Dehumidication
(1)ActivatedwhenRHexceeds2%ofthesetpoint,deactivatedwhenRHfallsbelow1%ofthesetpoint.
(2)ActivatedwhenRHexceeds6%ofthesetpoint,deactivatedwhenRHfallsbelow1%ofthesetpoint.
Table1.1OperatorpanelsystemparametersRH98
190TGB-1035-H1604Options45