EasyManua.ls Logo

Munters ML690 - 9.4 Sound data; Scrapping

Munters ML690
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DehumidierML420-MLT1400
9.4Sounddata
Figure9.3Ductconnections
1.Ductworkfordryair
2.Ductworkforprocessair
3.Ductworkforreactivationair
4.Ductworkforwetair
Denitions:
Lp(A)=Soundpressure(freeeld,DirectivityfactorQ=2,d=1distancefromsourceinmeter)
Lp(A)=Lw(A)+10Log(Q/(4πd²))
Lw(A)=SoundpowerleveldB(A-weighted)
9.4.1SounddataML420
Lp(A)at1mLw(A)Measurerange(Hz)
dBdB631252505001000200040008000
58667272656057605554
Table9.3Soundtoroom,allinletsandoutletsducted
DuctLw(A)Measurerange(Hz)
dB631252505001000200040008000
1.Dryair688879686157534841
2.Processair719380725959595250
3.Reactair769384807364575448
4.Wetair739583765748434027
Table9.4Soundinducts
36Technicalspecication190TGB-1035-H1604