Manual for MVK-MPNIO Modules
V 1.9 71
DI8 DI8 Art. No. 55256, 55268, 55528
B
us Data
Transfer protocol ................................................ PROFINET I/O
Transfer rates ..................................................... 100 Mbit/s
Addressing ......................................................... via DHCP
S
upply
Operating voltage U
B
......................................... 24 V DC
Supply voltage range ......................................... 18 ... 30 V DC
Current consumption (without inputs) ................ <150 mA at 24 V DC
Sensor supply .................................................... max. 200 mA per sensor
Short-circuit protection for sensors .................... Multifuse,
............................................................................ up to 100 mA load automatic start
............................................................................ from 100 mA load reset required
Tripping time multifuse ....................................... 1s at I
K
≥1 A and 23°C
Reverse polarity protection inputs ..................... Yes
I
nputs / diagnostics
No. of inputs ........................................................ 16
Delay time with signal change ........................... 2 to 5 ms
Input characteristics ........................................... EN 61131-2, type 2
Input filter ............................................................ approx. 1 ms
Over voltage protection ....................................... Yes (suppressor diode)
Reverse polarity protection 55268, 55528
Module electronics .............................................. Yes
Sensors ............................................................... No
Actuators ............................................................. No
R
everse polarity protection 55256
Module electronics .............................................. Yes
Sensors ............................................................... Yes
Actuators ............................................................. Yes