3.0 FURNACE OPERATION INFORMATION
Outlet Pressure Boss Regulator Vent
On/Off SwitchTerminals
Inlet Pressure
Boss (opt.)
Regulator
Adjust
FIGURE 3
3.1 STARTING THE FURNACE
H26.1
During the heating season, the operation o
f
the
f
urnace is
f
ully automatic.
1. First read these instructions and safety notices thoroughly.
2. Set the thermostat to below the current set point.
3. Ensure that all supply air registers and return air grills are open.
4. Turn off the electric power to the furnace.
5. Remove the burner access door.
6. Ensure that the furnace manual shut-off gas valve is in the “ON” position. The valve handle is normally
in-line with the gas pipe and valve body when it is in the “ON” position; perpendicular to the gas piping and
valve body when it is in the “OFF” position.
7. Turn the manual gas valve switch to the “OFF” position. (Figure 3)
8. Wait 5 minutes to clear out any gas. If, after this time you smell gas, STOP. Turn the appliance manual
shut-off valve to the “OFF” position. If burning LP gas, smell for gas near the oor since propane and
butane are both heavier than air. If after this time you do not smell gas, continue to the next step.
9. Turn the manual gas valve switch to the “ON” position.
10. Replace the burner access door, ensuring that it is properly in place.
11. Restore the electric power to the furnace.
12. Adjust the thermostat to the desired setting. If the thermostat also controls an air conditioning system,
ensure that the thermostat system switch is in the “HEAT” or “AUTO” mode.
If this is the rst time that the furnace has undergone a trial ignition since installation, or if there has been work
done on the gas lines, the furnace might not light because of air trapped in the gas supply line.
Simply turn the thermostat down to below the current set point, wait 5 minutes, then adjust the thermostat to
the desired setting. If the problem persists, proceed to “Furnace Shut-Down Procedure” and call your Installer,
service agency or gas supplier.
W415-0973 / B / 08.28.13
UM
64

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Napoleon 9600 Series and is the answer not in the manual?

Napoleon 9600 Series Specifications

General IconGeneral
AFUE Rating96%
Blower TypeVariable speed
Gas ValveModulating
Ignition SystemHot surface ignition
Fuel TypeNatural gas or propane
Heat ExchangerStainless steel
Blower MotorECM
Heat Exchanger WarrantyLifetime limited
Parts Warranty10 years
Vent Size2" or 3"
Stages2-stage
Heating Capacity40, 000 - 120, 000 BTU

Related product manuals