EasyManua.ls Logo

Nastec VASCO - Page 20

Nastec VASCO
34 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20
parameter
default
desciption
Constant press.
Fix speed
Const.press.2val
Fix speed 2 val.
External speed
Constant temp.
Constant flow
0.5
It's the increase of pressure respect to pressure
set which must be passed so that there is a forced
shutdown of the pump.
0.5
The common parameters than you should get the
temperature above the temperature set so that
the pump, arrested earlier, are restarted.
1
It's the temperature rise compared to
temperature set which must be passed so that
there is a forced shutdown of the pump.
0.5
This value represents the flow drop below the set
flow required to start the pump.
1
It's the increase of flow respect to flow set which
must be passed so that there is a forced
shutdown of the pump.
Kp and Ki parameters allow the dynamic control
of system by VASCO; set values (Ki=50, Kp=005)
are usually enough to get a valid dynamic control;
if the set pressure do not consent a valid control,
proceed as follows; increase or reduce Ki while
keeping Kp constant; if the problem persists,
increase Kp value and increase or reduce the Ki
value again till a good dynamic control is reached.
OFF
Function to activate (ON) the first auxiliary pump
DOL 1 (Direct On Line pump).
OFF
Function to activate (ON) the second auxiliary
pump DOL 2 (Direct On Line pump).
OFF
Function to allow alternating starting priority
between the DOL pumps in order to allow equal
use of them.
1
delay time with which the pumps DOL start after
the variable speed pump has reached the
maximum frequency and the pressure value has
fallen below set pressure delta start pressure
OFF
Function to enable multiple VASCO’s to work in
parallel as described in the technical appendix
(see the relevant chapter). Up to 8 VASCO units
can be connected in parallel.
VASCO’s communication through RS 485 gates is
granted by a private protocol.
Direct
Direct: increasing misured pressure, VASCO
decreases motor frequency.
Inverse: increasing misured pressure, VASCO
increase motor frequency.
PI control
Direct/Reverse
COMBO
ON/OFF
Start delay AUX
t = XX [s]
Alternance
ON/OFF
Pump DOL 2
ON/OFF
Pump DOL 1
ON/OFF
Kp
XXX
Ki
XXX
Delta stop flow
Q = XXX.X [m3/h]
Delta start flow
Q = XXX.X [m3/h]
Delta stop temp.
T = XXX.X [°C]
Delta start temp.
T = XXX.X [°C]
Delta stop press
p = XX.X [bar]

Related product manuals