It's the increase of pressure respect to pressure
set which must be passed so that there is a forced
shutdown of the pump.
The common parameters than you should get the
temperature above the temperature set so that
the pump, arrested earlier, are restarted.
It's the temperature rise compared to
temperature set which must be passed so that
there is a forced shutdown of the pump.
This value represents the flow drop below the set
flow required to start the pump.
It's the increase of flow respect to flow set which
must be passed so that there is a forced
shutdown of the pump.
Kp and Ki parameters allow the dynamic control
of system by VASCO; set values (Ki=50, Kp=005)
are usually enough to get a valid dynamic control;
if the set pressure do not consent a valid control,
proceed as follows; increase or reduce Ki while
keeping Kp constant; if the problem persists,
increase Kp value and increase or reduce the Ki
value again till a good dynamic control is reached.
Function to activate (ON) the first auxiliary pump
DOL 1 (Direct On Line pump).
Function to activate (ON) the second auxiliary
pump DOL 2 (Direct On Line pump).
Function to allow alternating starting priority
between the DOL pumps in order to allow equal
use of them.
delay time with which the pumps DOL start after
the variable speed pump has reached the
maximum frequency and the pressure value has
fallen below set pressure – delta start pressure
Function to enable multiple VASCO’s to work in
parallel as described in the technical appendix
(see the relevant chapter). Up to 8 VASCO units
can be connected in parallel.
VASCO’s communication through RS 485 gates is
granted by a private protocol.
Direct: increasing misured pressure, VASCO
decreases motor frequency.
Inverse: increasing misured pressure, VASCO
increase motor frequency.
PI control
Direct/Reverse
Start delay AUX
t = XX [s]
Delta stop flow
Q = XXX.X [m3/h]
Delta start flow
Q = XXX.X [m3/h]
Delta stop temp.
T = XXX.X [°C]
Delta start temp.
T = XXX.X [°C]
Delta stop press
p = XX.X [bar]