EasyManuals Logo

National Instruments NI USB-6008 User Manual

National Instruments NI USB-6008
30 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
© National Instruments Corporation 25 NI USB-6008/6009 User Guide and Specifications
Environmental
Temperature (IEC 60068-2-1 and IEC 60068-2-2)
Operating .......................................................0 to 55 °C
Storage ...........................................................40 to 85 °C
Humidity (IEC 60068-2-56)
Operating .......................................................5 to 95% RH, noncondensing
Storage ...........................................................5 to 90% RH, noncondensing
Pollution Degree (IEC 60664) ...............................2
Maximum altitude..................................................2,000 m
Indoor use only.
Safety
This product meets the requirements of the following standards of safety for electrical equipment for
measurement, control, and laboratory use:
IEC 61010-1, EN 61010-1
UL 61010-1, CSA 61010-1
Note For UL and other safety certifications, refer to the product label or the Online Product
Certification section.
Electromagnetic Compatibility
This product meets the requirements of the following EMC standards for electrical equipment for
measurement, control, and laboratory use:
EN 61326-1 (IEC 61326-1): Class A emissions; Basic immunity
EN 55011 (CISPR 11): Group 1, Class A emissions
AS/NZS CISPR 11: Group 1, Class A emissions
FCC 47 CFR Part 15B: Class A emissions
ICES-001: Class A emissions
Note In the United States (per FCC 47 CFR), Class A equipment is intended for use in commercial,
light-industrial, and heavy-industrial locations. In Europe, Canada, Australia and New Zealand (per
CISPR 11) Class A equipment is intended for use only in heavy-industrial locations.
Note Group 1 equipment (per CISPR 11) is any industrial, scientific, or medical equipment that
does not intentionally generates radio frequency energy for the treatment of material or
inspection/analysis purposes.
Note For EMC declarations and certifications, and additional information, refer to the
Environmental Management section.
CE Compliance
This product meets the essential requirements of applicable European Directives as follows:
2006/95/EC; Low-Voltage Directive (safety)
2004/108/EC; Electromagnetic Compatibility Directive (EMC)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the National Instruments NI USB-6008 and is the answer not in the manual?

National Instruments NI USB-6008 Specifications

General IconGeneral
BrandNational Instruments
ModelNI USB-6008
CategoryI/O Systems
LanguageEnglish

Related product manuals