92 Operating the Boiler
Item Description
21. Boiler Pump
Delay**
Set the space heating pump over-run
time.
Setting range: 3 – 40 min
Default: 40 min
22. DHW Demand
On Diff
When the DHW temperature sensor is
used:
Setting range: 0–10°C (0–18°F)
Default: 3°C (5°F)
23. DHW Demand
Off Diff
When the DHW temperature sensor is
used:
Setting range: 0–5°C (0–9°F)
Default: 0°C (0°F)
24. Service Notif Time
Set the time for service notification.
Setting range: 30 – 3650 days (10
years)
It can be set in 10 day increments.
Default: 1820 days (5 years)
25. Service Notif Cycl
Set the service notification according to
the operating times.
Setting range: 300 – 36500 cycles
It can be set in 100 cycle increments.
Default: 18200 cycles
26. Service contact # View the service contact information.
27. Factory Reset
Initialize all parameter settings (panel
and main controller) to factory default.
28. P/W Change
Change the parameter setting
password.
Rotate the Command dial (
) to
change numbers and places, and press
the Command dial (
) to save the new
password.
Item Description
12. DHW Min Limit
Set the DHW supply minimum
temperature.
Setting range: DHW minimum
capacity (%) – [DHW MAX capacity
limit - 20] %
Default: Boilers minimum heat
capacity
13. DHW Max Limit
Set the DHW supply maximum
temperature.
Setting range: [DHW Min capacity
limit + 20] % – 100%
Default: 100%
14. Freeze protection
Set the pump freeze protection
temperature.
Setting range: 43°F (6°C) – 50°F (10°C)
Default: 50°F (10°C)
Note
The system freeze protection
temperature is set based on
the pump freeze protection
temperature.
15. Low Sys Pressure
Set the low water system pressure.
Setting range: 4 – 17 psi
Default: 6 psi
16. High Sys Pressure
Set the high water system pressure.
Setting range: 40 – 80 psi
Default: 50 psi
17. Boiler pump
Oper(DHW)
Turn on or turn off the boiler pump in
DHW mode.
Setting range: On/Off
Default: Off
18. Sys pump
Oper(DHW)
Turn on or turn off the system pump in
DHW mode.
Setting range: On/Off
Default: Off
19. Zone2 pump
Oper(DHW)
Turn on or turn off Zone 2 pump in
DHW mode.
Setting range: On/Off
Default: Off
20. DHW pump
Oper(DHW pri)
Turn on or turn off the DHW pump
in DHW mode when both the space
heating and DHW demands are
present.
Setting range: On/Off
Default: On

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Navien NFB Series and is the answer not in the manual?

Navien NFB Series Specifications

General IconGeneral
TypeCondensing Boiler
Fuel TypeNatural Gas or Propane
Heat ExchangerStainless Steel
Vent TypeDirect Vent
Vent Diameter2" or 3"

Related product manuals