L-PAK 150/250 StandardEN
12
6 PLC sengs
6.1 Find a parameter and set its value
ESC OK
NEDERMAN
Hi Vacum Unit
L-PAK Standard
OFF
TimeTo Service
2000 Hours
ESC OK
Thu 10:45
2018-02-01
ESC OK
Stop >
>
Setup >
Network >
Diagnoscs >
Program
ESC OK
Set Parameter
Program Name
ESC OK
H-Meter >
ZV-Detect >
SSR_Time >
DIRTmr >
OTTmr Z
WeekTmr >
Do the following to nd a parameter and set its value:
1. From the PLC status screen, press the down arrow to go to the date and me
screen.
2. Press ‘Escape’
to go to the main menu.
3. Press the down arrow to go to ‘Program’. Press ‘OK’
to conrm.
4. Select ‘Set Parameter’. Press ‘OK’
to conrm.
5. Use the up or down arrows to nd the parameter. Press ‘OK’
to conrm.
6. Use the le and right arrows to select a value.
7. Use the up or down arrows to set the value. Press ‘OK’
to conrm.
8. Press ‘Escape’
to go to the main menu.
9. Press ‘Escape’
to go to go to the date and me screen.
10. Press the up arrow to exit.
NOTE! There are several other input menus on the same level as the date and me screen.
If pressing the down arrow
takes the PLC to one of those menus, use the le arrow to
get to the date and me screen.
NOTE! The blinking cursor shows the current value that can be changed.