L-PAK 150/250 Standard
15
EN
Example: 2 Cleaning pulses
On=2, Tch=5, Tpu=1 → On * (Tch + Tpu) = 2*(5+1) =12s where Tch=05:00s and Tpu=01:00s.
The default me for a complete cleaning cycle is 12 seconds
6.3 Standard Cleaning process
The lter cleaning process is always acvated aer the pilot signal (PS) or (PSIFC) has
disappeared and DIR Time has elapsed.
If ushing funcon is acvated, ushing will be done before lter cleaning takes place.
The lter cleaning valve opens and the lter cleaning process generates a preset number of
cleaning pulses. The unit then goes into Idle mode keeping cleaning valve open.
See funcon in secon
6.2.6. Clean cycle to set numbers of pulses and related parameters.
See funcon in secon
6.2.5. FCTmr to acvate Timer controlled Filter cleaning.
6.4 Warning-Alarm output Q4
Potenal free output Terminal X1:33-34.
When an alarm is acvated, Output Q4 and White lamp buon on the control box side
ash with interval 1 second on / 1 second o .
Warning -Alarm Output Q4, switch with an interval 1 second on / 1 seconds O, if one or
more of the alarms listed below are acve:
• The fan temperature is over 125°C see secon 5.3.1. Alarm! Fan Hi Temp.
• The motor is overheated see secon 5.3.2.Alarm!MotorProtectorAcvated.
• The compressed air level is low see secon 5.3.3. Alarm! Low Pressure CAS.
Warning -Alarm Output Q4, switch with an interval 1 second on /3 seconds O, if one or
more of the warnings listed below are acve:
• Warning Fan Hi Temp see 5.2.2. Warning! Fan Hi Temp.
6.5 Standby (Ready) indicator
The H1 lamp/Output DO1 acts as a Standby (unit ready) indicator. The H1 Lamp/DO1 is
acvated when the unit is in Standby mode or the fan is running. The H1 lamp/Output DO1
is available on terminal X1:3 and X1:4 for remote indicaon.