L-PAK 150/250 Standard
7
EN
4.2 Unit operaon modes
L-PAK 150/250 Advanced has the following four operaon modes:
1. O mode
2. Standby mode
3. Running mode
4. Idling mode
See Secon
5.1. Status messages for more informaon about each mode. How the unit
moves from one operaon mode to another is explained below. See also Figure 1 for a ow
chart showing how the unit goes through its four dierent operaon modes.
When the unit is in O mode, the unit can be put into Standby mode (the unit is ready)
with its motor o and the Filter Cleaning Valve (FCV) closed by pressing the Standby/
Running buon. While the unit is in Standby mode, the unit can be put back into O mode
again by pressing the Standby/Running buon.
The unit goes from Standby mode into Running mode when it receives a pilot signal by a
valve being opened at one or more work staons (in other words, someone starts to work).
The unit’s motor is now on and the FCV is closed. The DIR_Time and SSR_Time mers are
not started, see Secons
6.2.4. DIR_Time and 6.2.3. SSR_Time.
The unit stays in Running mode as long as there is an acve pilot signal. However, the unit
can sll be put into O mode by pressing the Standby/ Running buon.
Note that if only one workstaon is connected to the unit, or if only one work staon is
in use and work stops at that one staon, the pilot signal stops. If there is more than one
work staon connected to the unit, and more than one work staon is in use, the pilot
signal only stops if work stops at all workstaons (in other words, all valves close).
When the pilot signal stops, the DIR and SSR mers start. If work resumes at one or more
work staons within 10 seconds, the unit stays in Running mode. The DIR and SSR mers
are reset back to zero and are stopped.
If DIR_Time is set for 10 seconds (default), and the pause in work is longer than 10 seconds,
DIR_Time elapses. The unit then goes into Idling mode with its motor on and the FCV open.
If a new pilot signal is sent within 12 minutes, the unit goes back into Running mode. The
DIR and SSR mers are again reset to zero and are stopped. However, if SSR_Time is set for
12 minutes, which is the default seng, and there is no new pilot signal within 12 minutes,
SSR_Time also elapses.
The unit then goes into Standby mode unl it either receives a new pilot signal that puts
the unit back into Running mode, or the unit is turned o (in other words, put into O
mode) by pressing the Standby/Running buon.
5 PLC messages
The following secons show the dierent status, warning and alarm messages that can be
seen in the PLC display.
5.1 Status messages
The following status messages give informaon about what mode the unit is in or what
roune service is being performed.