L-PAK 150/250 StandardEN
14
6.2.3 SSR_Time
Menu for seng the SSR mer. The SSR mer is for the amount of me before the unit
goes from Idling mode to Standby mode when the pilot signal disappears.
ESC OK
SSR_Time 1/1
T = 12:00m
Ta = 00:00
T = 12:00m: Time before SSR_Time is acvated. The default seng is 12
minutes. The minimum seng is 5 minutes.
Ta = 00:00: The elapsed me since the pilot signal disappeared.
6.2.4 DIR_Time
Menu for seng the DIR mer. The DIR mer is the amount of me before the unit goes
from Running mode into Idling mode when the pilot signal disappears.
ESC OK
DIRTmr 1/1
T = 10:00s
Ta = 00:00
T = 10:00s: Time before DIR_Time is acvated. The default seng is 10
seconds The minimum seng is 5 seconds.
Ta = 00:00: The elapsed me since the pilot signal disappeared.
6.2.5 FCTmr
Menu for acvang and seng me between mer controlled lter cleaning.
ESC OK
FCTmr 1/1
Stat = ON
TH = 01:00s
TL = 60:00m
Stat =On Filter Cleaning mer acvated Default is On.
TH=01:00s: Do not change the default seng of 1 second.
TL=60:00m: Time between automac lter cleanings. The default seng
is 60 minutes.
Ta=00:00: The elapsed me since the last automac cleaning was
acvated.
6.2.6 Clean cycle
Menu for seng the opening and closing mes for the “FCV” Filter Cleaning Valve.
FCV cleaning cycle repeats X mes depend on value of parameter ‘On’.
This funcon is always acve when lter cleaning takes place.
ESC OK
Clean Cyc 1/1
Tch = 05:00s
Tpu = 01:00s
On = 1
Cnt =0
Tch = Vacuum Building me (Charge Time): Default is 5 seconds.
Tpu = Clean pulse me. Default 1 second.
On = Number of cleaning pulses.
Cnt = 0: Elapsed cleaning pulses.
NOTE! For the parameter ‘On’, the minimum value = 1.
NOTE! If On is set to 0, No lter cleaning is performed.
Time duraon for a cleaning cycle below:
Example: 1 Cleaning pulse
On=1, Tch=5, Tpu=1 → On * (Tch + Tpu) = 1*(5+1) =6s where Tch=05:00s and Tpu=01:00s.
The default me for a complete cleaning cycle is 6 seconds.