NW511
16
5.4 Modifiableparameters
Thistableliststhemodelchoiceorcycleandtemperatureoptionparameters.
F/M ID Description Default Notes
M P0 ApplianceType 05 Constructionversion
Donotmodify
F P1 ApplianceModel 05 Donotmodify
M P2 Boilertemperature 80C Step1degree
WARNING:Theactualboiler
temperaturedependson
whethertheconnectionis
single‐phaseorthree‐phase.
Withthree‐phaseconnection,
donotsetmorethan85°
M P3 Tanktemperature 58C Step1degree
M P4 Thermostopoption 01 0=off1=on
M P5 SoftStartoption 01 0=off1=on
M P6 Boilertemperature
offset
00 Real=measured+Offset
M P7 Tanktemperature
offset
04 Real=measured+Offset
M P8 Realtemperature
display
01 0=filtered,1=real
F P9 Tankprobetype 01 Donotmodify
NoteforP6andP7:negativenumbersareindicatedbyilluminationofbothdecimalpoints(e.g.:‐12
“1.2.”)
5.5 Alarmtriggertimethresholds
Thistablelistsallthesafetydevicetriggertimethresholds.
F/
M
ID Description Default
Min
.
Max
Notes
F A0
F A1 Boilermax.heatingtime 20min 5 60 Step=1min
F A2 Tankmax.heatingtime 60min 5 60 NotactivewithPLON
F A3 Maximumwaterintaketime 5min 1 20 Step=1min
F A4 Maximumemptyingwaittime 1min 1 2 Step=1min