Page 7
Installing the UPS
Note: Before installing the UPS, a quick disconnect
method for AC power should be installed near the
UPS at the AC Input by a licensed electrician.
Required Items
• UPS with AC and DC cables
• UPS battery
• Can wrench (thin-walled 7/16” socket
wrench) (included)
• Site-supplied mounting hardware (see
appendix)
• Phillips head screwdriver
• Wire strippers
• Adjustable wrench or socket set (for wall or
strut mounting)
Instructions
1. Mount the UPS to a pole, wall, or strut
channel.
2. Ground UPS in accordance with local
regulations/code using the included
grounding wire.
3. Unlock the UPS door using the can (thin-
walled) socket wrench.
4. Run the DC cable through the pre-punched
¾” (19 mm) hole at the bottom of the UPS
enclosure via the cable gland.
5. Strip the DC cable (coming from the PoE
injector or gateway) and connect the DC
Negative wire to the negative DC output
terminal on the UPS and tighten the screw.
Connect the stripped DC positive wire to the
positive DC output terminal on the UPS and
tighten the screw.
6. Place the battery inside the UPS box between
the battery strap brackets and apply
corrosion inhibitor to the battery terminals.
7. Secure the red UPS battery wire to the
positive battery terminal and the black UPS
battery wire to the negative battery terminal
using the included bolts and washers.