ses.status.displayError
Description
This message occurs when the SES module in the disk shelf detects an error in the disk
shelf display panel. The disk shelf might be unable to provide correct addresses to the disk
shelf.
Corrective action
1. If possible, verify that the connection between the disk shelf and the display is secure.
2. Verify that the SES module or modules are fully seated; replacing them might solve the
problem.
3.
If the problem persists, the SES module that detected the error condition might be faulty.
4.
If the problem persists after the module or modules are replaced, replace the disk shelf.
5.
If the problem persists, contact technical support.
ses.status.displayWarning
Description
This message occurs when the enclosure services module detects a warning condition for
the disk shelf display panel. The disk shelf might be unable to provide correct addresses to
its disks.
Corrective action
1. If possible, verify that the connection between the disk shelf and the display is secure.
2. Verify that the SES module or modules are fully seated; replacing them might solve the
problem.
3. If the problem persists, the SES module that detected the warning condition might be
faulty.
4. If the problem persists after the module or modules are replaced, replace the disk shelf.
5. If the problem persists, contact technical support for assistance.
ses.status.temperatureError
Description
This message occurs when the indicated disk shelf temperature sensor reports a temperature
that exceeds the specifications for the disk shelf or its components.
Corrective action
1. Verify that the ambient temperature where the shelf is installed is within the vendor's
equipment specifications by using the environment shelf [adapter] command,
and check that airflow clearances are maintained.
For clustered systems, you must run this command from the nodeshell of the target
node.
2. If the same disk shelf also reports fan or fan module failures, correct that problem
immediately.
3. If the problem is reported by the ambient temperature sensor (located on the operator
display panel), verify that the connection between the disk shelf and the panel is secure,
if possible.
4. If the problem persists, and if the shelf has multiple temperature sensors but only one
exhibits the problem, replace the module that contains the sensor reporting the error.
5. If the problem persists, contact technical support.
DS4243, DS2246, DS4486, and DS4246 Installation and Service Guide 36
Monitoring disk shelf components

Table of Contents

Other manuals for NetApp DS4246

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the NetApp DS4246 and is the answer not in the manual?

NetApp DS4246 Specifications

General IconGeneral
Data transfer rate6 Gbit/s
Storage drive size3.5 \
Storage drive interfaceSerial Attached SCSI (SAS)
Storage drives installedYes
Installed storage drive typeHDD
Supported storage drive typesHDD & SSD
Total installed storage capacity40.8 TB
Maximum supported storage capacity- TB
Number of storage drives installed24
Chassis typeRack (4U)
Product colorBlack
Device classLarge Enterprise Business
AC input voltage100-240 V
AC input frequency50 - 60 Hz
Number of power supply units2
Operating altitude0 - 3045 m
Non-operating altitude-305 - 12192 m
Storage temperature (T-T)-40 - 70 °C
Operating temperature (T-T)10 - 40 °C
Storage relative humidity (H-H)10 - 95 %
Operating relative humidity (H-H)20 - 80 %
Weight and Dimensions IconWeight and Dimensions
Depth610 mm
Width483 mm
Height178 mm