24
5.1.2 Outputs - General
Click the picture of the output to open detailed settings.
The General tab configures basic parameters for controlling the output.
Figure 15 ā General output configuration
Output name is shown above the two control buttons to improve clarity.
Short ON/OFF delay is an integer specifying, in milliseconds, the duration for the Short OFF (power
cycling) and Short ON actions.
During this interval, any attempts to switch the output state via M2M API protocols are ignored.
Output PowerUp state defines the state of the output whenever the device is powered up or
restarted. The output can be switched on (ON), switched off (OFF), or set to the last state before the
restart (LAST). The PowerUp setting is ignored if the Scheduler is enabled for specific output.