7
3 Specifications
Power
100-240 V; 50/60 Hz; 16 A - PowerBOX 3PE, PowerBOX 4KE
100-240 V; 50/60 Hz; 16 A - PowerBOX 3PF, PowerBOX 4KF
100-240 V; 50/60 Hz; 13 A - PowerBOX 3PG, PowerBOX 4KG
Switched outputs
16 A in total / 16 A each output - PowerBOX 3PE, PowerBOX 4KE
16 A in total / 16 A each output - PowerBOX 3PF, PowerBOX 4KF
13 A in total / 13 A each output - PowerBOX 3PG, PowerBOX 4KG
Maximum line breaker
capacity
C16A PowerBOX 3PE, PowerBOX 4KE
C16A PowerBOX 3PF, PowerBOX 4KF
C13A PowerBOX 3PG, PowerBOX 4KG
Fuse
Integrated, non-resettable
Surge protection
Type 3 (CAT III)
Power Output relays
Micro-disconnection (µ) (resistive load), SPST-NO
1E5 switching cycles, max. 1.5 kV pulse voltage
Switch heat and fire resistance class 1
Electrical load
PowerBOX 3Px: ZVS (Zero Voltage Switching)
- most load types, such as switching power supplies compatible
PowerBOX 4Kx: ZCS (Zero Current Switching)
- Resistance load compatible
- Capacitive load compatible
- Inductive load compatible
Network interfaces
1x Ethernet RJ-45 10/100 Mbit/s
Attention! Device connected over LAN must be connected in
network with same earth potential (PE).
Internal consumption
Max 2W
Environment
IP30, protection rating = class 1
Operating temperature -20°C to 65°C / 10A
-20°C to 50°C / 16A
Device rated for pollution degree 2.
Designed for continuous operation in altitudes up to 2000 m.
Does not require additional cooling