NOTE
Only mark the option for ground water pump
if the accessory AXC 40 is to be used to control
the circulation pump.
8 Room sensor settings
VWDUW JXLGH
IDFWRU V\VWHP
FRQWURO URRP VHQVRU V\VW
FRQWURO URRP VHQVRU V\VW
FRQWURO URRP VHQVRU V\VW
FRQWURO URRP VHQVRU V\VWHP
URRP VHQVRU VHWWLQJV
factor system
Setting range: 0.2 - 3.0
Default value: 2.0
Room sensors to control the room temperature can be
activated here.
Here you can set a factor that determines how much the
supply temperature is to be affected by the difference
between the desired room temperature and the actual
room temperature. A higher value gives a greater change
of the heating curve's set offset.
If several climate systems are installed the above settings
can be made for the relevant systems.
9 Setting of exhaust air module FLM
VWDUW JXLGH
WLPH EHWZHHQ GHIURVWV
PRQWKV EWZQ ILOWHU DODUPV
FRQWLQXRXV SXPS RS
)/0
KUV
This part of the start guide is only displayed if the altern-
ative is selected in a previous menu and the accessory is
installed.
time between defrosts
Setting range: 1 – 30 h
Default value: 10 h
months btwn filter alarms
Setting range: 1 – 12
Default value: 3
continuous pump op.: Select for continuous operation
of the circulation pump in the exhaust air module.
time between defrosts: Set the minimum time that
must pass between defrostings of the heat exchanger in
the exhaust air module.
When the exhaust air module is in operation the heat
exchanger is cooled so that ice builds up on it. When too
much ice builds up the heat transfer capacity of the heat
exchanger is reduced and defrosting is required. Defrost-
ing warms up the heat exchanger so that the ice melts
and runs off via the condensation hose.
months btwn filter alarms: Set how many months
should pass before the heat pump informs that it is time
to clean the filter in the exhaust air module.
Clean the exhaust air module's air filter regularly, how
often depends on the amount of dust in the ventilation
air.
10 Setting the fan speed exhaust air
VWDUW JXLGH
VSHHG
VSHHG
VSHHG
VSHHG
QRUPDO
IDQ VS H[KDXVW DLU
NIBE™ F1145Chapter 6 | Commissioning and adjusting28