TIP
The value can be increased if you have, for
example, a cellar that you always want to heat,
even in summer.
You may also need to increase the value in
"stop heating" menu 4.9.2 "auto mode setting".
MENU 1.9.4 - ROOM SENSOR SETTINGS
factor system
heating
Setting range: 0.0 - 6.0
Factory setting heating: 1.0
cooling (accessory required)
Setting range: 0.0 - 6.0
Factory setting cooling: 1.0
Room sensors to control the room temperature can be
activated here.
Caution
A slow heating system such as underfloor
heating may not be suitable for control using
the installation’s room sensors.
Here you can set a factor (a numerical value) that determ-
ines how much an over or sub normal temperature (the
difference between the desired and actual room temper-
ature) in the room is to affect the supply temperature
to the climate system. A higher value gives a greater
and faster change of the heating curve's set offset.
NOTE
Too high a set value for "factor system" can
(depending on your climate system) produce
an unstable room temperature.
If several climate systems are installed the above set-
tings can be made for the relevant systems.
MENU 1.9.5 - COOLING SETTINGS (ACCESS-
ORY REQUIRED)
cool/heat sensor
Factory setting: no sensor selected
set pt value cool/heat sensor
Setting range: 5 - 40 °C
Default value: 21
heat at room under temp.
Setting range: 0.5 - 10.0 °C
Default value: 1.0
cool at room over temp.
Setting range: 0.5 - 10.0 °C
Default value: 3.0
larm rumsgivare kyla
Setting range: on/off
Factory setting: off
start passive cooling
Setting range: 10 – 500 DM
Factory setting: 30 DM
start active cooling
Setting range: 10 – 300 DM
Factory setting: 90 DM
step difference compressors
Setting range: 10 – 150
Default value: 30
degree minutes cooling
Setting range: -3000 – 3000 cooling degree minutes
Factory setting: 0
heat dump 24h-function
Setting range: on/off
Factory setting: off
closingtime for cool dump
Setting range: 0 - 100 s
Factory setting: 0 s
max compr. in active cooling
Setting range: 0 - 18
Factory setting: 18
NIBE F1345Chapter 3 | Control - Menus16