EasyManua.ls Logo

Nibe F1345 - Page 16

Nibe F1345
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TIP
The value can be increased if you have, for
example, a cellar that you always want to heat,
even in summer.
You may also need to increase the value in
"stop heating" menu 4.9.2 "auto mode setting".
MENU 1.9.4 - ROOM SENSOR SETTINGS
factor system
heating
Setting range: 0.0 - 6.0
Factory setting heating: 1.0
cooling (accessory required)
Setting range: 0.0 - 6.0
Factory setting cooling: 1.0
Room sensors to control the room temperature can be
activated here.
Caution
A slow heating system such as underfloor
heating may not be suitable for control using
the installation’s room sensors.
Here you can set a factor (a numerical value) that determ-
ines how much an over or sub normal temperature (the
difference between the desired and actual room temper-
ature) in the room is to affect the supply temperature
to the climate system. A higher value gives a greater
and faster change of the heating curve's set offset.
NOTE
Too high a set value for "factor system" can
(depending on your climate system) produce
an unstable room temperature.
If several climate systems are installed the above set-
tings can be made for the relevant systems.
MENU 1.9.5 - COOLING SETTINGS (ACCESS-
ORY REQUIRED)
cool/heat sensor
Factory setting: no sensor selected
set pt value cool/heat sensor
Setting range: 5 - 40 °C
Default value: 21
heat at room under temp.
Setting range: 0.5 - 10.0 °C
Default value: 1.0
cool at room over temp.
Setting range: 0.5 - 10.0 °C
Default value: 3.0
larm rumsgivare kyla
Setting range: on/off
Factory setting: off
start passive cooling
Setting range: 10 500 DM
Factory setting: 30 DM
start active cooling
Setting range: 10 300 DM
Factory setting: 90 DM
step difference compressors
Setting range: 10 150
Default value: 30
degree minutes cooling
Setting range: -3000 3000 cooling degree minutes
Factory setting: 0
heat dump 24h-function
Setting range: on/off
Factory setting: off
closingtime for cool dump
Setting range: 0 - 100 s
Factory setting: 0 s
max compr. in active cooling
Setting range: 0 - 18
Factory setting: 18
NIBE F1345Chapter 3 | Control - Menus16

Related product manuals