Compressor blocked due to the temperature condi-
tions.
Wait until the temperature is within the product’s
working range.
Minimum time between compressor starts has not
been reached.
Wait for at least 30 minutes and then check if the
compressor has started.
Alarm tripped.
Follow the display instructions.
"Additional heat only" is selected.
Switch to "Auto" or "Manual" in menu 4.1 "Operating
mode".
WHINING NOISE IN THE RADIATORS
Closed thermostats in the rooms and incorrectly set
heating curve.
Set the thermostats to max. in as many rooms as
possible. Adjust the heating curve via menu 1.1, in-
stead of choking the thermostats.
Circulation pump speed set too high.
Enter menu 5.1.11 (pump speed heating medium)
and reduce the speed of the circulation pump.
Uneven flow over the radiators.
Adjust the flow distribution between the radiators.