Nibe F1345 - Page 65

Nibe F1345
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
May be due
to/check
Resets automatic-
ally when
Heat pump action.CauseText in displayNo.
Open-circuit or
short-circuit on
sensor input.
Defective sensor
Calculation of cool-
ing DM performed
with EQ1-BT25 is
set to 0.
The input for the
sensor receives un-
reasonably high or
low value for longer
than 2 seconds.
Flt: EQ1-BT25323
Undersized heat-
ing system.
Incorrectly adjus-
ted heating curve.
Incorrect flow.
Incorrectly connec-
ted additional
heat.
Resets automatic-
ally when the tem-
perature is below
70 °C.
Heating is blocked.The maximum tem-
perature from the
heat pump is ex-
ceeded.
hi. temp. out333
Undersized heat-
ing system.
Incorrectly adjus-
ted heating curve.
Incorrect flow.
Incorrectly connec-
ted additional
heat.
Resets automatic-
ally when the tem-
perature is below
60 °C.
Heating is blocked.The maximum tem-
perature through
the heat pump is
exceeded. BT3 is
higher than 65 °C in
heating operation
high in temp.334
Open-circuit or
short-circuit on
sensor input.
Defective sensor
Resets automatic-
ally when the
sensor has worked
continuously for 60
seconds.
The input for the
sensor receives an
unreasonably high
or low value for
longer than 2
seconds when the
sensor is activated.
Sensor fault on
BT50 room
sensor.
350
Manual.Change from auto
to manual brine
pump speed.
Delta BT10-
BT11>|2K| after cal-
ibration.
Failed sensor cal-
ibration
351
Manual.Change from auto
to manual pump
speed.
Delta BT3-
BT12>|2K| after cal-
ibration.
Failed sensor cal-
ibration
353
Manual.None.Alarm from the gas
boiler (GBM).
Int temp OPT er-
ror
359
Open-circuit or
short-circuit on
sensor input.
Defective sensor
Resets automatic-
ally when the
sensor has worked
continuously for 60
seconds.
The input for the
sensor receives un-
reasonably high or
low value for longer
than 2 seconds.
Sensor fault:
EPxx-BT3 return
line sensor
361-
367
Open-circuit or
short-circuit on
sensor input.
Defective sensor
Resets automatic-
ally when the
sensor has worked
continuously for 60
seconds.
None.The input for the
sensor receives un-
reasonably high or
low value for longer
than 2 seconds.
Sensor fault:
EP12-BT57/BT58
369-
370
65Chapter 5 | Disturbances in comfortNIBE F1345