climate system 1 to 8
The value for the change is set in menu 1.9.2, "ex-
ternal adjustment".
activation of one of four fan speeds.
The following five options are available:
1-4 is normally open (NO)
1 normally closed (NC)
The fan speed is activated during the time the switch
is closed. Normal speed is resumed when the switch
is opened again.
SG ready
Caution
This function can only be used in mains net-
works that support the "SG Ready" standard.
"SG Ready" requires two AUX inputs.
“SG Ready” is a smart form of tariff control, which
allows your electricity supplier to affect the indoor,
hot water and/or pool temperatures (if applicable) or
simply block the additional heat and/or compressor in
F1355 at certain times of the day (can be selected in
menu 4.1.5 after the function is activated). Activate
the function by connecting potential-free switch
functions to two inputs selected in menu 5.4
(SG Ready A and SG Ready B).
Closed or open switch means one of the following:
Blocking (A: Closed, B: Open)
"SG Ready" is active. The compressor in the heat
pump and additional heat is blocked like the day's
tariff blocking.
Normal mode (A: Open, B: Open)
"SG Ready" is not active. No effect on the system.
Low price mode (A: Open, B: Closed)
"SG Ready" is active. The system focuses on costs
savings and can for example exploit a low tariff from
the electricity supplier or over-capacity from any own
power source (effect on the system can be adjusted
in the menu 4.1.5).
Overcapacity mode (A: Closed, B: Closed)
"SG Ready" is active. The system is permitted to run
at full capacity at over capacity (very low price) with
the electricity supplier (effect on the system is set-
table in menu 4.1.5).
(A = SG Ready A and B = SG Ready B )
External blocking of functions
An external switch function can be connected to F1355
for blocking various functions. The switch must be po-
tential-free and a closed switch results in blocking.
NOTE
Blocking entails a risk of freezing.
Functions that can be blocked:
heating (blocking of heating demand)
compressor (blocking of EP14 and EP15 can be com-
bined. If you want to block both (EP14) and (EP15),
this will occupy two AUX inputs).
hot water (hot water production)
additional heat (additional heat is blocked)
tariff blocking (additional heat, compressor, heating,
cooling and hot water are disconnected)
31Chapter 5 | Electrical connectionsNIBE F1355