EasyManuals Logo

Nibe F1355 Series User Manual

Nibe F1355 Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #41 background imageLoading...
Page #41 background image
Technical specifications
IP 21
3X400 V
F1355-28Model
Output data according to EN 14511 nominal (50 Hz)
0/35
20.77kWHeating capacity (P
H
)
4.56kWSupplied power (P
E
)
4.55-COP
0/45
19.87kWHeating capacity (P
H
)
5.54kWSupplied power (P
E
)
3.59-COP
10/35
26.68kWHeating capacity (P
H
)
4.76kWSupplied power (P
E
)
5.60-COP
10/45
25.71kWHeating capacity (P
H
)
5.84kWSupplied power (P
E
)
4.40-COP
Output data according to EN 14825
28kWP
designh
, 35 °C / 55 °C
5.4 / 4.2-SCOP cold climate, 35 °C / 55 °C
5.0 / 4.0-SCOP average climate, 35 °C / 55 °C
Energy rating, average climate
A++ / A++The product’s room heating efficiency class 35 °C / 55 °C
1)
A+++ / A+++Space heating efficiency class of the system 35 °C / 55 °C
2)
Electrical data
400V 3N ~ 50HzRated voltage
22.1A
rms
Max operating current, heat pump
3)
9.5 / 8.5A
rms
Max. operating current compressor EP14 / EP15
25ARecommended fuse rating
27.7A
rms
Starting current
-ohmMax permitted impedance at connection point
4)
6 360WTotal output, brine pumps
3)
5 174WTotal output, HM pumps
IP 21Enclosure class
Refrigerant circuit
R407C / R407CType of refrigerant EP14 / EP15
2.2 / 2.0kgFill amount EP14 / EP15
1,774GWP refrigerant
3.90 / 3.55tonCO
2
equivalent EP14 / EP15
3.2 (32 bar)MPaCut-out value pressostat HP
-0.7 (-7 bar)MPaDifference pressostat HP
0.15 (1.5 bar) / 0.08 (0.8 bar)MPaCut-out value, pressure switch LP EP14 / EP15
0.15 (1.5 bar) / 0.07 (0.7 bar)MPaDifference, pressure switch LP EP14 / EP15
0.13 (1.3 bar)MPaCut-out value, pressure transmitter LP
0.01 (0.1 bar)MPaDifference, pressure transmitter LP
Brine circuit
0.6 (6 bar)MPaMax system pressure brine
1.19l/sNominal flow
95kPaMax external avail. pressure at nominal flow
1.55l/sFlow at P
designh
80kPaExternal available pressure at P
designh
see diagram°CMin/Max incoming Brine temp
-12°CMin. outgoing brine temp.
Heating medium circuit
0.6 (6 bar)MPaMax system pressure heating medium
41Chapter 8 | Technical dataNIBE F1355