Technical specifications
F2015-11F2015-8F2015-6Type
9.4/2.67.1/1.85.4/1.4(kW)Delivered/supplied power* at 2/35 °C **
11.1/2.68.2/1.96.3/1.4(kW)Delivered/supplied power* at 7/35 °C **
7.1/2.95.0/2.13.7/1.6(kW)Delivered/supplied power* at -7/45 °C **
8.8/3.16.4/2.14.9/1.6(kW)Delivered/supplied power* at 0/45 °C **
10.9/3.27.8/2.26.0/1.7(kW)Delivered/supplied power* at 7/45 °C **
7.1/3.24.9/2.33.6/1.7(kW)Delivered/supplied power* at -7/50 °C **
9.2/3.46.6/2.45.0/1.8(kW)Delivered/supplied power* at 2/50 °C **
10.8/3.67.6/2.45.9/1.8(kW)Delivered/supplied power* at 7/50 °C **
12.8/3.69.2/2.47.2/1.9(kW)Delivered/supplied power* at 15/50 °C **
5.3/2.83.7/2.02.6/1.5(kW)Delivered/supplied power* at -15/45 °C **
10.9/2.88.0/1.96.1/1.5(kW)Delivered/supplied power at 7/35 °C ***
3.954.154.21COP at 7/35 °C ***
271917(A)Starting current
221614(A)Motor protection setting
included as standardSoft-start relay
230 V 1AC 50HzOperating voltage
Scroll compressorCompressor
0.250.200.16(l/s)Nominal flow heating medium
2.21.51.3(kPa)Internal pressure drop at nominal flow
0.5/2.5(bar)Min-/max pressure heating medium side
1700/20001700/20001500(m
3
/h)Airflow
90/13090/13070(W)Nominal output, fan
252020(A)Fuse
IP 24Enclosure class
60(°C)Max outgoing heating medium temperature
2.12.11.9(kg)Refrigerant volume (R407C)
G1 (Ø 28 mm)Connection heating medium male Ø
hot gas defrostingDefrosting system
29(bar)Cut-out value pressostat HP
0.3(bar)Cut-out value pressostat LP
-7(bar)Difference pressostat HP
+0.7(bar)Difference pressostat LP
1045(mm)Height with stand
1200(mm)Width
520(mm)Depth
132126120(kg)Weight
dark greyColour
-15/45 (-15/45)(°C)Lowest operational point, outdoor air/flow line
35/58(°C)Highest operational point, outdoor air/flow line
064 015064 014064 044Part No.
Compressor, fan and control. Flows according to EN 255.
Defrosting reduces the relationship between input/output
by about 10 %.
*
outside temperature/Flow temperature**
According to EN 14511***
33F2015
Miscellaneous
Technical specifications