May be due toDescriptionAlarm text on the dis-
play
Alarm
The fan cannot rotate freely
Defective control board in F2040
Defective fan motor
Control board in F2040 dirty
Fuse (F2) blown
Deviations in the fan speed in F2040.Fan alarm224
Sensor does not work (see section
"Ambient temperature sensor")
Insufficient air circulation or heat ex-
changer
Blocked
If the fault persists during cooling,
there may be an insufficient amount
of refrigerant.
Defective control board in F2040
Temperature deviation on the hot gas
sensor (Tho-D) twice within 60 minutes
or for 60 minutes continuously.
Continuously high hot
gas
230
F2040 not powered
Fault in the communication cable.
Communication fault with accessory
board
Communication error254
Sensor does not work (see section
"Disturbances in comfort")
Insufficient air circulation or blocked
heat exchanger
Defective control board in F2040
Too much refrigerant
Temperature deviation on the heat ex-
changer sensor (Tho-R1/R2) five times
within 60 minutes or for 60 minutes
continuously.
High temperature in heat
exchanger
261
Can occur when 15V power supply to
the inverter PCB is unstable.
When IPM (Intelligent power module)
displays FO-signal (Fault Output) five
times during a 60-minute period.
Power transistor too hot262
Incoming power supply interference
Service valve closed
Insufficient amount of refrigerant
Compressor fault
Defective circuit board for inverter in
F2040
Voltage from the inverter outside the
parameters four times within 30 minutes.
Inverter error263
Open circuit in connection between
boards
Defective circuit board for inverter in
F2040
Defective control board in F2040
Communication between circuit board
for inverter and control board broken.
Inverter error264
Defective fan motor
Defective circuit board for inverter in
AMS 10
Continuous deviation on power transistor
for 15 minutes.
Inverter error265
Service valve closed
Loose connection sensor (BT15, BT3)
Defective sensor (BT15, BT3)
Too little refrigerant
Insufficient refrigerant is detected upon
start-up in cooling mode.
Insufficient refrigerant266
Defective circuit board for inverter in
F2040
Defective control board in F2040
Compressor fault
Failed start for compressorInverter error267
NIBE™ F2040Chapter 9 | Alarm list40