May be due toDescriptionAlarm text on the dis-
play
Alarm
Open circuit or short circuit on sensor
input
Sensor does not work (see section
"Disturbances in comfort")
Defective control board AA23 in F2040
Sensor fault, Sensor incoming water in
F2040 (BT3).
Sensor fault BT33
Open circuit or short circuit on sensor
input
Sensor does not work (see section
"Disturbances in comfort")
Defective control board AA23 in F2040
Sensor fault, Sensor outgoing water in
F2040 (BT12).
Sensor fault BT1212
Open circuit or short circuit on sensor
input
Sensor does not work (see section
"Disturbances in comfort")
Defective control board AA23 in F2040
Sensor fault, Sensor fluid pipe in F2040
(BT15).
Sensor fault BT1515
Low flow during heating operation
Too high set temperatures
Too high temperature out from the con-
denser. Self-resetting.
High condenser out162
Temperature generated by another
heat source
Too high temperature into the condens-
er. Self-resetting.
High condenser in163
Set when the heat pump runs the de-
frosting procedure
Not an alarm, but an operating status.Defrosting in progress183
Insufficient air circulation or blocked
heat exchanger
Open circuit or short circuit on input
for high pressure switch (63H1)
Defective high pressure switch
Expansion valve not correctly connec-
ted
Service valve closed
Defective control board in F2040
Low or no flow during heating opera-
tion
Defective circulation pump
Defective fuse, F(4A)
The high pressure switch (63H1) de-
ployed 5 times within 60 minutes or for
60 minutes continuously.
HP alarm220
Open circuit or short circuit on input
for low pressure sensor
Defective low pressure sensor
Defective control board in AMS 10
Open circuit or short circuit on input
for suction gas sensor (Tho-S)
Defective suction gas sensor (Tho-S)
Too low value on the low pressure sensor
3 times within 60 minutes.
LP alarm221
Any circuit breakers for AMS 10 off
Incorrect cable routing
Communication between the control
board and the communication board is
interrupted. There must be 22 volt direct
current (DC) at the switch CNW2 on the
control board (PWB1).
OU Com. error223
39Chapter 9 | Alarm listNIBE™ F2040
9 Alarm list

Other manuals for Nibe F2040

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nibe F2040 and is the answer not in the manual?

Nibe F2040 Specifications

General IconGeneral
TypeAir/water heat pump
RefrigerantR410A
Operating Temperature Range Heating-20°C to 35°C
Operating Temperature Range Cooling10°C to 46°C
Sound Power Level56-62 dB(A) (depending on model)

Related product manuals