Summary
Preface P. 6
Chapter 2 P. 17
Technical data
Chapter 5 P. 76
Reception, storage
and installation
Chapter 4 P. 54
General information
Chapter 3 P. 47
Application notes
Chapter 6 P. 115
Options
Chapter 7 P. 129
Preventive maintenance
Chapter 1 P. 15
Overview
and installation diagram
Answer Drives 1000
129
7
Preventive maintenance is the set of operations to preserve the AD1000
drive against wear phenomena and premature ageing.
The criteria that inspires these operations programming are independent
from preventing random failures, which still can occur.
The table lists the maintenance sheets, time intervals, and the operation to
be performed.
7 PREVENTIVE MAINTENANCE
TABLE 7.1.1 MAINTENANCE OPERATIONS SUMMARY
SYSTEM SUBGROUP OPERATION CODE TIME INTERVALS
Drive AD1000 - Cleaning AD1000-PM001 1 month
Drive AD1000 Boards Cleaning AD1000-PM002 1 month
Drive AD1000 Jumper Check AD1000-PM003 6 months
Drive AD1000 Radiator Cleaning AD1000-PM004 1 month
Drive AD1000 Fans Cleaning AD1000-PM005 3 years
Drive AD1000 Capacitors Formatting AD1000-PM006 -
after first installation
and then every year