EasyManua.ls Logo

Nidec Unidrive HS72 - Page 28

Nidec Unidrive HS72
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
28 Unidrive M702 / HS72 Control Getting Started Guide
Issue Number: 4
00.025 Preset Reference 2 ±VM_SPEED_FREQ_REF rpm 0.0
RW
00.026
Preset Reference 3
±VM_SPEED_
FREQ_REF Hz
0.0
RW
Uni M:Overspeed
Threshold
0 to 40000 rpm
0.0
RW
Uni HS: Overspeed
Threshold
0 to 50000 rpm
00.027
Preset Reference 4
±VM_SPEED_
FREQ_REF Hz
0.0
RW
P1 Rotary Lines Per
Revolution
1 to 100000 1024 4096
RW
00.028 Enable Auxiliary Key 0 to 2 0
RW
00.029
NV Media Card Data
Previously Loaded
0 to 999
RO
00.030 Parameter copying
None (0), Read (1), Program (2),
Auto (3), Boot (4)
None (0)
RW
00.031 Drive Rated Voltage 200 V (0), 400 V (1), 575 V (2), 690 V (3)
RO
00.032
Maximum Heavy Duty
Rating
0.000 to 99999.999 A
RO
00.033
Catch A Spinning Motor
Disable (0),
Enable (1),
Fwd Only (2),
Rev Only (3)
Disable (0)
RW
Motor Parameter Adaptive
Control
0 to 2 0
RW
00.034 User Security Code
0 to 2
31
-1
0
RW
00.037 Active IP Address 000.000.000.000 to 255.255.255.255
RO
00.038 Current Controller Kp Gain 0 to 30000 20 150
RW
00.039 Current Controller Ki Gain 0 to 30000 40 2000
RW
00.040 Auto-tune 0 to 2 0 to 3 0 to 4 0
RW
00.041
Maximum Switching
Frequency
2 kHz (0), 3 kHz (1), 4 kHz (2), 6 kHz (3),
8 kHz (4), 12 kHz (5), 16 kHz (6)
3kHz (1)
RW
00.042 Number Of Motor Poles Automatic (0) to 480 Poles (240) Automatic (0) 6 Poles (3)
RW
00.043
Rated Power Factor 0.000 to 1.000 0.850
RW
Position Feedback Phase
Angle
0.0 to
359.9°
RW
00.044 Rated Voltage ±VM_AC_VOLTAGE_SET
200 V drive: 230 V
50 Hz default 400 V drive: 400 V
60 Hz default 400 V drive: 460 V
575 V drive: 575 V
690 V drive: 690 V
RW
00.045
Uni M: Rated Speed 0 to 33,000 rpm
0.00 to
33,000.00
rpm
50Hz
default:
1500 rpm
60Hz
default:
1800 rpm
50Hz
default:
1450 rpm
60Hz
default:
1750 rpm
RW
Uni HS: Rated Speed 0 to 180,000 rpm
0 to
50,000 rpm
Motor Thermal Time
Constant 1
1.0 to
3000.0 s
89.0 s
RW
00.046 Rated Current ±VM_RATED_CURRENT Maximum Heavy Duty Rating (11.032)
RW
00.047
Uni M: Rated Frequency 0.0 to 550.0 Hz
50Hz default: 50.0 Hz
60Hz default: 60.0 Hz
RW
Uni HS: Rated Frequency 0.0 to 3000 Hz
0.0 to
1667 Hz
00.048 Drive Mode
Open-loop (1), RFC-A (2),
RFC-S (3), Regen (4)
Open-loop
(1)
RFC-A (2) RFC-S (3)
RW
Parameter
Range Default
Type
*
OL RFC-A RFC-S OL RFC-A RFC-S